THScope ( Logiciel )

Management and Diagnostics for Industrial Networks

TH SCOPE is a software product for industrial network management and network diagnostics. Geared to plant operators and maintenance personnel, TH SCOPE is an all-in-one, easy-to-use solution for permanent monitoring and predictive maintenance, for acceptance testing and for troubleshooting. Combined with TH LINK components, the product supports PROFIBUS, PROFINET, EtherNet/IP and Modbus TCP protocols.
The PROFINET Commissioning Report functionality is now available in new THSCOPE Release. Download the new THSCOPE under ‘Downloads’ section.
THScope ( Logiciel )

Versatile Solution for a Wide Variety of Diagnostics Applications

  • Network commissioning, acceptance testing
  • Stationary operation for continuous monitoring
  • Fault localization and identification in case of failure

Comprehensive Representation and Analysis of Diagnostic Data

  • Data on network communication (e.g. load, error statistics)
  • Data from network configuration (e.g. device names, firmware versions, topology)
  • Diagnostic messages (network and device diagnostics)
  • Data collection also from standard Ethernet devices (e.g. PCs or camera systems)

Optimized for Maintenance Users

  • Easy and intuitive handling and operation
  • No expert knowledge of IT or networks required
  • Support of various network protocols (PROFIBUS, PROFINET, EtherNet/IP, Modbus TCP)

Flexible Integration into Existing Systems and Processes

  • Integration of network data into monitoring tools and supervisory control systems via SNMP or OPC
  • Export of all diagnostic data, support of further processing in applications such as Excel
  • Web-based access, local or remote
Functionality
  • Network overview with network and device status plus diagnostic messages with troubleshooting recommendations
  • Analysis of device logs
  • Live list, statistics, inventory
  • GSDML file support, plaintext messages in diagnostic list
  • Topology and trend analysis
  • Automatic e-mail notification in case of fault
  • Reference comparison
  • Acceptance measurements and acceptance reports
  • Data export via Excel
Supported Protocols PROFIBUS (TH SCOPE V2.2),
PROFINET, EtherNet/IP, Modbus TCP (TH SCOPE V2.2 and TH SCOPE V3.0)
Interfaces
  • SNMP Agent
  • OPC Classic DA Server
System Requirements
  • Web browser with Adobe Flash Player 14 or higher
    (for TH SCOPE V2.2, not required for TH SCOPE V3.0)
  • Adobe Reader 8 or higher for reading the documentation and for printing the topology
Supported Operating Systems Windows 7, Windows 8, Windows 8.1,
Windows Server 2008, Windows Server 2008 R2, Windows Server 2012, Windows Server 2012 R2
Network Access Data collection through TH LINK (PROFIBUS, PROFINET, EtherNet/IP, Modbus TCP and Industrial Ethernet)
Demo Version Full TH SCOPE functionality can be used for free for 30 days after installation
Licensing Via software or hardware key
 Scope of Delivery
Software TH SCOPE (by download from Softing‘s website)
License Software or hardware key
Documentation Installation Manual, User Manual, Release Note
Order Numbers
ATV-LRA-JY-003024 TH SCOPE (software key)
ATV-LRL-JY-003025 TH SCOPE (hardware key)
Additional Products and Services
ATV-GEA-JN-003006 TH LINK PROFIBUS
ATV-GDA-JA-003034 TH LINK PROFINET
ATV-GDA-JY-003037 TH LINK Industrial Ethernet
ATV-LRA-JY-003028 TH LINK PC Industrial Ethernet

TH SCOPE:
If your network is protected by a second firewall in addition to the Windows firewall, make sure that the following settings are made to allow TH SCOPE services to communicate properly.

  • Enabling of HTTP port 80 – inbound and outbound
  • Enabling of SNMP port 161 inbound or port 2367 (if port 161 is used by another SNMP agent).
  • Enabling of IP 224.0.5.128 port 2364 UDP outbound
  • Enabling of UDP ports 2365 outbound and 2366 inbound

 

The following ports are used by TH SCOPE for internal communication only:

  • Port 22
  • Port 80
  • Port 1100
  • Ports 1123 – 1151
  • Port 1500
  • Port 1501
  • Ports 2363 – 2366
  • Ports 49152 – 49171

People interested in this product, can be interested in :

THLink – Industrial Ethernet

Outil de diagnostic : Industrial Ethernet, indépendant du contrôleurs

Le THLink Industrial Ethernet, permet le contrôle et le diagnostic des réseaux PROFINET, MODBUS TCP et ETHERNET/IP. Les données sont collectées sur un réseua de 254 noeuds et  rendent disponibles ses données via le logiciel  THSCOPE. le THLINK Industrial Ethernet est facile à utiliser et peut être intégré sans interférer avec une installation existante

THLink - Industrial Ethernet

THLink Industrial Ethernet for an independent Access to PROFINET, EtherNet/IP and Modbus TCP Networks

  • Controller-independent
  • Independent of configuration tools
  • Only one tool needed to monitor multiple IP subnetworks (up to 254 nodes, one or more controllers

THLink Industrial Ethernet has been designed for Installation without Interference with Plant Operation

  • Connection to free port in industrial network, also possible during operation of the plant
  • No need to install TAPs or use mirror ports
  • Highest security (separate accesses for control room level and plant level, no routing)
  • Easy integration into existing plants thanks to compact design

Powerful Data Collection Capabilities Optimized for Ethernet-Based Industrial Communication

  • Support of the PROFINET, EtherNet/IP and Modbus TCP protocols
  • Collection also from standard Ethernet devices (e.g. PCs or camera systems)
  • PROFINET supervisor in PROFINET networks
  • Network load limit according to PROFINET guidelines

Optimized for Use by Maintenance Engineers, thanks to the THLink industrial Ethernet

  • Suitable for network acceptance testing, continuous monitoring and troubleshooting
  • Easy and intuitive handling and operation
  • Fault identification with intelligent troubleshooting assistance
  • Seamless integration with TH SCOPE diagnostics software
Functionality
  • Network detection and data collection
  • Alarm notification in case of fault
  • Basic monitoring, configuration
  • Integrated web server
Input Voltage 24 VDC (18 VDC … 32 VDC)
Current consumption max. 180 mA
Current consumption relay contact max. 100 mA
Operating Temperature -40 °C … +75 °C
Relative Air Humidity 5 … 95 % (no condensation)
Ethernet Ports RJ-45 (10Base-T/100Base-TX)
Supported SD Cards See Release Notes
Mounting 35 mm DIN rail
Dimensions (HxWxD) 22.5 x 99 x 114.5 mm
Weight 120 g
Certifications CE
GDA-JY-003037 TH LINK Industrial Ethernet

Scope of Delivery

Hardware TH LINK Industrial Ethernet
Documentation Installation Manual, Release Note (by download)

Additional Products and Services

ATV-LRA-JY-003024 TH SCOPE (software key)
ATV-LRL-JY-003025 TH SCOPE (hardware key)
ATV-LRA-JY-003028 TH LINK PC Industrial Ethernet (software key)
ATV-LRL-JY-003029 TH LINK PC Industrial Ethernet (hardware key)
ATV-TRA-PN-TECH Training “PROFINET Technology”
ATV-TRA-PN-CERTENG Training “PROFINET Commissioning and Troubleshooting”

OPC UA C++ Development Toolkit pour Windows

OPC UA C++ Windows : Outils de développement

OPC UA windows : Fast Time-to-Market for OPC UA Clients and Servers

  • OPC UA Communication Integration in Windows-based Automation Environments
  • Comprehensive Functionality Provided by Libraries
  • Optimal Total Costs of Ownership Through All-In-One License Model

OPC UA Windows : Complete Solution Addressing All Customer Requirements

  • Comprehensive set of building blocks offering encapsulation and easy-to-use functionality required for implementing OPC UA Clients and Servers for Windows environment
  • Modular design to scale OPC UA functionality according to actual requirements
  • Wide range of available functionality, including Extended Security, Data Access, Complex Data, Events, Alarms & Conditions and Historical Access
  • Integrated security concepts allowing safe remote data transfer actively addressing modern security threats
  • Applicable for time-critical control tasks as well as for complex automation projects
  • OPC UA Servers and Clients capable to move data and information between factory floor and enterprise level

Comprehensive Scope of Delivery for Easy and Fast Development

  • Optimized Application Programming Interface (API) and easy to understand documentation
  • Complimentary how-to example applications, step by step tutorials, complex test and simulation clients and servers for a lean getting started with OPC UA development

Investment Security Through Innovative License Model

  • Implementation according latest OPC UA Client respectively OPC UA Server specifications
  • Free migration to upcoming OPC UA Development Toolkit versions thanks to toolkit software and 3 years‘ right to updates to future versions
  • Technology proven by use in Softing‘s OPC Server and middleware products
OPC Specifications OPC Unified Architecture V1.03
OPC Roles OPC UA Client, OPC UA Server
OPC UA Client Profiles Core Characteristics, Data Access, Complex Data, Base Eventing, Methods, Audit, Historical Access, Alarms and Conditions, Query, Redundancy
OPC UA Server Profiles Core Characteristics, Data Access, Complex Data, Base Eventing, Methods, Audit, Historical Access, Alarms and Conditions
OPC UA Transport OPC UA TCP transport; UA Binary Encoding, UA Secure Conversation
HTTPS transport; UA Binary Encoding
OPC UA Security Security policy: Basic256Sha256/Basic256/Basic128Rsa15/None
Authentication: anonymous/user name and password/user certificate
Full compliance to OPC UA 1.03 specification
OPC UA Modelling Model designer as helper tool for address space configuration for OPC UA Servers
Programming Interface* C++
Development Environment* Microsoft Visual Studio 2008, Microsoft Visual Studio 2010 (x86 and x64), Microsoft Visual Studio 2013 (x86 and x64), Microsoft Visual Studio 2015 (x86 and x64) , Microsoft Visual Studio 2017 (x86 and x64)
Development Operating Systems* Windows 7 (32 Bit and 64 Bit), Windows 8.1 (32 Bit and 64 Bit), Windows 10 (32 Bit and 64 Bit), Windows Server 2008 R2, Windows Server 2012
Target Operating Systems* Windows 7 (32 Bit and 64 Bit), Windows 8.1 (32 Bit and 64 Bit), Windows 10 (32 Bit and 64 Bit), Windows Server 2008 R2, Windows Server 2012, Windows Embedded
Compliance / Certification OPC Foundation certification for Server, regularly tested at OPC Foundation interoperability workshops
Support Tools Comprehensive programming examples and tutorials, complex test and simulation OPC UA Server and Client applications, generic technology test and demonstration Client and Server tools
Trial Version Trial toolkit assemblies contain complete functionality. Limitation to 90-minute runtime period applies.
Trial version upgrades to unlimited functionality simply by using binary license activation key.
Licensing Trial and evaluation license, single seat developer license (binary and source code version)
Applications integrating licensed toolkit libraries can be deployed in unlimited number of copies.

* Please contact the Softing sales representative for requests of different compilers or operating system variants.

Downloads

ATV-LMA-DD-035101 Service and Support Contract for OPC UA C++ Client Toolkit for Windows, 3 years minimum period, based on yearly fee, including single seat developer license WRL-DD-035101, binary format
ATV-WRL-DD-035101 OPC UA C++ Client Toolkit for Windows, single seat developer license, binary format, available only in combination with LMA-DD-035101
ATV-LMA-DD-035102 Service and Support Contract for OPC UA C++ Server Toolkit for Windows, 3 years minimum period, based on yearly fee, including single seat developer license WRL-DD-035102, binary format
ATV-WRL-DD-035102 OPC UA C++ Server Toolkit for Windows, single seat developer license, binary format, available only in combination with LMA-DD-035102
ATV-LMA-DD-035201 Service and Support Contract for OPC UA C++ Client Toolkit for Windows, Source Format, Minimum Duration 3 Years, Includes WRL-DD-035101 license package
ATV-WQL-DD-035201 OPC UA C++ Client Toolkit for Windows, single seat developer license, source format, available only in combination with LMA-DD-035201
ATV-LMA-DD-035202 Service and Support Contract for OPC UA C++ Server Toolkit for Windows, 3 years minimum period, based on yearly fee, including single seat developer license WQL-DD-035202, source format
ATV-WQL-DD-035202 OPC UA C++ Server Toolkit for Windows, single seat developer license, source format, available only in combination with LMA-DD-035202
ATV-LEA-DD-030300 Site License extension for OPC Development Toolkits

Scope of Delivery

Software Installation package on Softing OPC Toolkits DVD-ROM, installation package available for download
Support Dedicated Support Team
Documentation Reference Manual in English in CHM format as part of installation package

Additional Products and Services

ATV-OPC-ENTW-TAG OPC Engineering / Consulting / Compliance Assistance
ATV-TRA-OPC-UA OPC UA Introductory Training for Decision Makers and Technical Leaders
ATV-LRL-DY-134501 dataFEED OPC Suite, Version 4.01 and higher

From OPC Data Access to OPC Unified Architecture

The latest edition of the OPC Book provides an excellent overview of the fundamentals, implementation and application of standardized data exchange via OPC. A key focus is on the new OPC generation – OPC Unified Architecture – that allows for platform-independent data and information exchange.

  • Comprehensive Overview of OPC
  • Detailed Introduction to OPC UA
  • Tools and Demo Programs
Order the Book: From Data Access to Unified Architecture

Comprehensive Overview of Specifications and applications

The OPC Book provides an introduction to all OPC Specifications released by the OPC Foundation, from the very first to the most recent. OPC stands for Openness, Productivity and Collaboration, symbolizing the new possibilities opening up in automation technology. In addition to the fundamentals of OPC, the book discusses the implementation of OPC servers and clients, and presents application possibilities and examples. This gives readers a comprehensive overview of OPC technology and application areas.

The New OPC Generation – OPC Unified Architecture

A key focus of the book is on the OPC Unified Architecture (OPC UA). The new OPC generation allows service oriented, multivendor, and cross-platform capable data and information exchange. Among the most important subjects here are the specifications of this Windows-independent technology, the OPC UA application possibilities, the development of OPC UA products for Windows, Linux and VxWorks operating systems, and the migration from OPC Classic to OPC UA. The book provides a solid foundation of knowledge for readers to build and use products supporting OPC UA in automation.

Tools and Demo Programs on CD-ROM

The included CD-ROM contains demo versions of a variety of OPC servers and OPC tools. It also provides several demonstration programs for development, commissioning, testing, and for the simulation of OPC clients and servers. Another major part of the CD-ROM is dedicated to OPC UA introductory videos and presentations. The comprehensive content makes it easy for readers to get started with OPC Classic and OPC UA.

Contents

  • Introduction
  • Fundamentals – Classic OPC Specifications, OPC Unified Architecture, Companion Standards, OPC Compliance Testing
  • Implementation – Base Technologies and Architecture Concepts, Implementation of Classic OPC Components, Implementation of OPC UA Components
  • Application – Classic OPC Product and Application Samples, Aspects of Use of Classic OPC Products, OPC UA Product, Samples, Performance

Summary and Outlook

Scope of Delivery

OPC Book with CD-ROM

Order the Book: From Data Access to Unified Architecture

TH Link PROFIBUS

TH Link PROFIBUS

TH Link PROFIBUS

Administration et gestion de réseaux avec analyse de réseaux Profibus

Accéder aux réseaux PROFIBUS avec une application FDT, AMS d’Emerson et TH Scope de Softing

THLINK PROFIBUS  fournit un accès indépendant du controlleur, aux réseaux PROFIBUS, pour la gestion et la maintenance.  L’outil supporte à la fois : la gestion du réseaux mais aussi l’analyse du réseaux Profibus.. THLINK PROFIBUS est facile d’utilisation et s’intègre très facilement avec le réseau PROFIBUS existant.

Independent Access to PROFIBUS Network

  • Controller-independent
  • Independent of configuration tools
  • Access for plant asset management applications to configure field devices based on FDT/DTM and EDDL standards (acyclic master)

Designed for Installation without Interference with Plant Operation

  • Connection to PROFIBUS network also possible during operation of the plant
  • Easy integration into existing plants thanks to compact design
  • Browser access for administration and configuration purposes

Powerful Data Collection Capabilities Optimized for PROFIBUS

  • Passive listening to PROFIBUS DP protocol
  • Threshold monitoring for frame retries
  • Statistics for optimization of the network configuration
  • Easy detection of missing terminating resistors

Optimized for Use by Maintenance Engineers

  • Central and time-saving parameterization of PROFIBUS and HART field devices directly from the control room
  • Continuous monitoring and troubleshooting for PROFIBUS networks
  • Fault identification with intelligent troubleshooting assistance
  • Seamless integration with TH SCOPE diagnostics software
Functionality
  • Network detection and data collection (PROFIBUS DP)
  • Acyclic master (PROFIBUS DP-V1)
  • Alarm notification in case of fault
  • Basic monitoring, configuration
  • Integrated web server
Supported Plant Asset Management Applications e.g.:

  • Endress+Hauser FieldCare
  • Emerson AMS Suite
  • Yokogawa Fieldmate
  • PACTware
PROFIBUS Transmission Rate
  • max. 12 MBit/s (AMS Device Manager, FDT)
  • max. 1.5 MBit/s (TH SCOPE)
Input Voltage 24 VDC (19.2 VDC … 28.8 VDC)
Current consumption max. 190 mA
Operating Temperature 0 °C … 50 °C
PROFIBUS interface RS 485
Ethernet Port RJ-45 (10Base-T/100Base-TX)
Mounting 35 mm DIN rail
Dimensions (H x W x D) 22.5 x 99 x 114.5 mm
Weight 120 g
Certificate CE
  • GEA-JN-003006 TH LINK PROFIBUS

    Scope of Delivery

    Hardware TH LINK PROFIBUS
    Documentation Installation Manual, Release Notes (by download)

    Additional Products and Services

    LRA-JY-003024 TH SCOPE (software key)
    LRL-JY-003025 TH SCOPE (hardware key)
    LRA-NN-021980 DTM Library
    VAA-YY-023000 PACTware
    VAA-NM-023001 TACC

dataFEED EdgeGate

dataFEED EdgeGate : Connexion de vos PLCs Siemens et Modbus vers IoT Hubs

Passerelle pour connecter vos PLCs Siemens et Modbus vers un Cloud. Communication Bidirectionnel et hautement sécurisée vers la suite Microsoft Azure IoT

dataFEED edgeGate est la passerelle connectant les réseaux industriels vers des applications IT, fonctionnant « on premise » ou sur le Cloud.

La passerelle EdgeGate connecte vos PLCs with des applications OPC UA.  edgeGate connecte vos PLCs au Cloud, via le protocole MQTT. De plus la passerelle offre une intégration à de spécifique IoT Hubs Avec son standard OPC UA, la configuration est simple et la sécurité est optimale. La passerelle EdgeGate est facile et rapide à mettre en oeuvre avec de petites solutions et permets d’évoluer vers une charge plus importante.

Connection of IoT Hubs with Siemens and Modbus PLCs

  • Adjustable topic settings for MQTT payload
  • Perform analytics, monitoring, and create globally available dashboards in cloud solutions from different vendors, e.g. Amazon AWS, IBM Bluemix, Microsoft Azure
  • Integration of OPC UA and MQTT client applications running on-premise as well as in private and public clouds
  • Worldwide remote access to field data
  • Suited to new applications such as IoT or analytics
  • Use edgeGate for migration or retrofit upgrades
  • No PLC programming necessary
  • Symbol import from STEP 7 and TIA Portal projects
  • No software updates, operating system patches, or PC updates required

Integration with Microsoft Azure

  • Direct data access from Microsoft Azure to Siemens and Modbus PLCs
  • Bidirectional data exchange between cloud and shop floor by accessing OPC UA Servers on edgeGate or in OT network via integrated Microsoft OPC Proxy and Publisher components

Industry-proven Security

  • Physically separate interfaces and separate configuration rights for OT and IT networks preventing intrusions
  • Supporting security standards as SSL/TLS and X.509 certificates
  • OPC UA compliant data encryption and user authentification
Hardware Processor Altera Cyclone V SoC with Dual-core ARM Cortex-A9
Connectors 2 x IEEE 802.3 100BASE-TX/10BASE-T (independent interfaces)
Status LEDs PWR (power supply), RUN (running), ERR (error), SYS (configuration)
Dimensions (H x W x D) 100 mm x 22.5 mm x 105 mm
Power Supply 18 VDC … 32 VDC, SELV/PELV supply mandatory Typically 200 mA, maximum 1 A at switch-on
Operating Temperature, Horizontal DIN Rail Installation -40 °C .. 50 °C (0 mm minimum distance)
-40 °C .. 55 °C (22.5 mm minimum distance)
Operating Temperature, Vertical DIN Rail Installation -40 °C .. 35 °C (0 mm minimum distance)
-40 °C .. 40 °C (22.5 mm minimum distance)
Storage Temperature -40 °C .. 85 °C
Relative Humidity 10 % … 90 %, non-condensing
Weight About 0.2 kg
Mounting DIN Rail (35 mm)
Housing Phoenix Contact ME MAX
Protection Class IP20
Software IT Network / Cloud Connectivity OPC UA (Server, 60,000 items in total), MQTT (Publisher, up to 1,000 topics)
Controller Connectivity RFC1006, Modbus TCP
Maximum Number of Controllers 5
Supported IoT Hubs Microsoft Azure connected factory, Microsoft Azure IoT Hub, IBM Watson IoT Hub, General Electric Predix, Amazon AWS, etc.
Supported Controllers Siemens S7-300, S7-400, S7-1200, S7-1500
Modbus TCP-compatible controllers (Schneider Electric, Wago, Beckhoff, Phoenix Contact, etc.)
Supported Engineering Tools SIMATIC STEP 7, TIA Portal V13, V13 SP1, V14, V14 SP1
Conformity Emission EC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 55011, Group 1, Class A EC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 55022, Class A EC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 61000, Part 6-4 FCC CFR45, Part 15 Section 15.107 and 15.109 (Class A), VCCI Class A Information Technology Equipment 2002
Immunity EC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 61000, Part 6-2

Téléchargement

  • Drivers & Logiciels

    • dataFEED Exporter ( Freeware)  Software for simple symbol import out of Siemens STEP7 or TIA-Portal Projects
  • Manuels & Documentation

  • Brochure

GAA-YY-145122 edgeGate

Scope of Delivery

Hardware edgeGate
Software Tool for configuration over integrated web interface, dataFEED Exporter for easy symbol import from Siemens Project Files
Documentation Quick Startup Guide (printed documentation)

Consultez nous pour des formations sur ce produit

epGatePN

epGatePN : Passerelle Ethernet IP -> PROFINET

Passerelle Ethernet IP vers PROFINET

Integration d’esclaves  PROFINET I/O via un mapping dans les systèmes de contrôles Ethernet IP

 

La passerelle epGatePN, élabore une passerelle entre un réseau Ethernet IP et jusqu’à 32 esclaves PROFINET. Alors qu’une des ports RJ45 se connecteau réseau Ethernet IP, l’autre port de la passerelle agit comme un controleur PROFINET. Il permet l’intégration de produits PROFINET à un réseau existant Ethernet IP. L’outil de configuration disponible, permet de définir la configuration PROFINET, d’utiliser les symboles et le « mapping » pour la/les PLCs Ethernet IP. Ainsi l’utilisateur est déchargé des taches suspectibles d’erreurs et défini individuellement l’accès aux données des 2 cotés de la passerelle.

Solutions similaires:
epGate DP: Integration de segments PROFIBUS DP dans un système Ethernet/IP
epGate PA: Integration de 4 segments PROFIBUS PA dans un système Ethernet/IP
epGate PB: Integration de 2 segments PROFIBUS PA  & 1 segment PROFIBUS DP dans un système Ethernet/IP

epGatePN

Simple Integration Through Add-On Instructions

  • Data access of PLC program to PROFINET Devices without requiring detailed PROFINET knowledge
  • Mapping between the two protocols generated by provided tools
  • Usage of Add-On Instructions (AOI), containing detailed PROFINET data type definitions
  • Transparent communication overcoming protocol differences

Time Saving Configuration Creation and Verification

  • Configuration tool for online access to PROFINET Devices via the network
  • Easy assignment of device properties
  • Early identification of discrepancies between offline configuration and real situation

Built-In Web Server For Monitoring And Interaction

  • Status information about both protocols
  • Monitoring of mapping as well as of exchanged data
  • Individual modification of FG-260 settings, including address information
  • Download and upload of all FG-260 configuration information using web server

Different Use Cases are addressed

  • Direct access from Ethernet/IP Scanner in the PLC to PROFINET field devices
  • Access to machines with internal PROFINET network by deploying I-Device capabilities
Hardware
Processor Altera Cyclone V SoC with Dual-core ARM Cortex-A9
Status LEDs (Gateway) PWR (power supply), RUN (running), ERR (error), CFG (configuration upload)
Status LEDs (EtherNet/IP) Net (network), Mod (module)
Status LEDs (PROFINET) SF (system fault), BF (bus fault)
Connectors 2 x IEEE 802.3 100BASE-TX/10BASE-T (1 Ethernet port per protocol)
Dimensions (HxWxD) 100 mm x 35 mm x 105 mm
Weight ca 0.25 kg
Power Supply 18 VDC … 32 VDC, SELV/PELV supply mandatory
Typically 200 mA, maximum 1 A at switch-on
Operating Temperature, Horizontal DIN Rail Installation -40 °C … 55 °C (0 mm minimum distance)
-40 °C … 65 °C (17.5 mm minimum distance)
Operating Temperature, Vertical DIN Rail Installation -40 °C … 40 °C (0 mm minimum distance)
-40 °C … 50 °C (17.5 mm minimum distance)
Storage Temperature -40 °C … 85 °C
Relative Humidity 10 % … 90 %, non condensing
Cooling Convection, no fan
Mounting DIN Rail (35 mm)
Protection Class IP20
Software
Protocols EtherNet/IP Adapter (Up to 2 input and 2 output assemblies with up to 255 Bytes data each, minimum RPI: 8 ms)
PROFINET Controller (up to 8 devices at 1 ms cycle time)
Additional Functionality Mapping application, web server
Supported Versions of Rockwell Automation PLC Programming Software V16 – V21
Emission Conformity EC Directive 2004/108/EG “Electromagnetic Compatibility“, EN 55011, Group 1, Class A
EC Directive 2004/108/EG “Electromagnetic Compatibility“, EN 55022, Class A
EC Directive 2004/108/EG “Electromagnetic Compatibility“, EN 61000, Part 6-4
FCC CFR45, Part 15 Section 15.107 and 15.109 (Class A),
VCCI Class A Information Technology Equipment 2002
Immunity Conformity EC Directive 2004/108/EG “Electromagnetic Compatibility“, EN 61000, Part 6-2
Certifications CE
EN/IEC 61010-1 and CB
EN/IEC 61010-2-201 and CB
UL 61010-1 and UL 61010-2-201
GCL-CA-010260 FG-260

Scope of Delivery

Hardware Passerelle epGatePN
Software EDS File, Outils de configuration et outils de recherche sur CD
Documentation Quick Startup Guide documentation, User Guide sur CD-ROM

People interested in this product, might be interested in :

THLink Profinet

echocollect -e

La passerelle echocollect -e

La passerelle Echocollect est une passerelle dédiée à l’intégration des données « Process Data » vers des systèmes de hauts niveaux ou de solutions IoT.

La passerelle echocollect -e est une passerelle multi protocoles fournissant des solutions de managment « Process Data ». Elle offre des connexions « temps réel » entre PLC et bases de données,  OPC UA et OPC Classic connectivité. Ses fonctionnalités inclues à la fois le log de données locales et une intégration directe de données d’applications Cloud IoT via MQTT

 

 

Vous ne connaissez pas l’ echocollect ???

Présentation Echocollect  ( PDF )

Integration of Existing Systems in New Quality Assurance Systems

  • Independent real-time collection of manufacturing, process or quality data directly from programmable logic controllers (PLC) and delivery to higher-level management systems, such as ERP or MES system
  • Recipe manager functionality for writing data blocks to PLCs
  • Direct connectivity via SQL database protocols, platform independent OPC UA technology or MQTT Publisher functionality
  • Support of more than 50 PLC types addressable via Ethernet

Excellent Data and Network Security

  • Buffering of arriving data and addition of time stamps in case of broken connections, automatic forwarding once connection has been reestablished
  • Option for parallel data logging on SD card for traceability reasons
  • Physical network separation between production systems and commercial IT networks
  • State-of-the-art OPC UA security: Optional encryption of transmitted data and authentication via certificates

Lowered IT Maintenance Costs and Investment Protection

  • echocollect as standard component, addition of extra functionality without modifying existing systems
  • No need for additional PC requiring software updates and administration
  • Working for years once configured – untouched, without updates and with zero maintenance costs
  • Plug-and-go replacement, if necessary, using configuration stored on SD card
  • Very easy configuration by straightforward project import without requiring PLC modifications and programming skills

Easy Live Data Visualization

  • Native web technology for easy and cost-efficient visualization of process, manufacturing and quality data using standard web browser without any plug-ins
  • No need for OPC Server or complex SCADA system
  • Scalable, resolution-independent vector graphics for consistent display of data on wide variety of network enabled devices like desktop PCs, laptops, smart phones, tablet PCs or industrial control panels
Ethernet Addressable Controllers Siemens SIMATIC S7 and S5, controllers with Modbus TCP (Wago, Beckhoff, Phoenix Contact, Schneider Electric, etc.), Mitsubishi (Melsec-Q), etc.
Ethernet Protocols TCP/IP, RFC1006 (ISO on TCP), ISO (H1), S5, S7, TCP/IP with PLC header, Modbus TCP, Melsec-Q, raw data
Ethernet Interfaces 2 x independent interfaces TP (RJ45), 10/100 MBit/s
Embedded OPC UA Server Symbolic Mapping; Browsing, Read, Write, Subscribe; Self-Discovery Service; possible reconfiguration without device restart; possible multiple Client connections, optional read-only PLC connection; OPC UA Security with password or certificates
Embedded MQTT Publisher Establishment of MQTT Broker connection, optional user authentication and data encryption, easy topic generation from existing symbols, maximum of 1,000 topics, adjustable publishing interval
Supported Databases MySQL, Oracle, DB2, MS-SQL
Other Protocols Telnet, SMTP (email notification), OPCpipe (OPC Tunnel)
Supported Engineering Tools for Symbol Import SIMATIC STEP 7, TIA Portal
Limitation Maximum of 5 PLC connections, 10,000 items in total
Data mapping PLC – database must be structured in 400 tables and 200 items per table
Visualization atvise webMI visualization, functional level ‘Advanced’ (fully event-driven data exchange) Limited to up to 50 visualized items per echocollect (optional upgrade possible), maximum of 5 simultaneously accessing browsers
Configuration Software Softing NetCon for device configuration, atvise builder for SCADA project editing, dataFEED Exporter for symbol import
Power Supply 24 VDC, ca. 0,3 A
Ambient Conditions Operating temperature: 0 °C … 55 °C, storage temperature: -20 °C … 70 °C
Dimensions (HxWxL) 131mm x 47mm x 111mm
Weight ca. 0,4 kg
Mounting 35 mm DIN Rail
Protection Class IP20
Certifications CE
GAL-YY-143101 echocollect e (connectors: 2 x Ethernet, 1 x TTY)
LRA-YY-143001 Upgrade echocollect: License for database access to Oracle, DB2 and MSSQL (default: MySQL only)
LRA-YY-143002 Upgrade echocollect: License enabling data logging on SD Card (default: no data logging)
LRA-YY-143004 Upgrade echocollect: License supporting unlimited number of visualization items (default: maximum of 50 visualization items)
LRA-YY-143005 Upgrade echocollect: License embedded OPC UA Server (default: no embedded OPC UA Server)
LRA-YY-143007 Upgrade echocollect: License MQTT Publisher functionality (default: no MQTT support)
LRA-YY-143115 Upgrade echocollect: License enabling maximum of 15 PLC connections (default: maximum of 5 PLC connections)

Additional Products and Services

700-5596-04 AC Adapter, 24 VDC, Euro, UK, or USA
LRL-DY-131701 OPCpipe client
MEA-YY-144002 CD atvise elements, 4,000 high-quality bitmaps and vector graphics in SVG format
GPL-CS-191000 echolink sS7-compact
110-1000-01 Industrial Ethernet – Troubleshooting in Automation, 3 days

Scope of Delivery

Hardware Multi-protocol gateway echocollect e, SD card, connector for power supply*
Software Net configuration software on CD-ROM, also downloadable from Softing website
Documentation Quick Start leaflet, context-based online help, CD-ROM with product handbook and configuration tutorials, also downloadable from Softing website

Connector Power Pack 24 V DC

Country-specific connector power packs are available. Note: A connector power pack is not included in the delivery of the echocollect. If necessary please order it separately. echocollect -e

Technical Details

100 – 240 V AC, 47 – 63 Hz, sec. 24 V, 1,25A

Order Number

Version EURO, UK, USA
700-5596-04

Which cloud platforms are supported?

We support with all Softing gateways (echocollect, uaGate, edgeGate) the Microsoft Azure Cloud, Amazon AWS Cloud, IBM Bluemix Cloud and other cloud providers, which are using MQTT for telemetry data.

What is the size of the Store & Forward queue on the echocollect?

The S&F queue for MQTT is unlimited (except the size of the sd-card). The echo buffers in the ram, and after it collects a bunch of messages, they were copied to the sd-card. To use the S&F feature, QoS 1 or QoS 2 must be used.

Les personnes intéressées par ce produit, peuvent être intéressées par :

BC-502-PB

Le BC-502-PB – pour PROFIBUS DP

BC-502-PB : moniteur de reseau PROFIBUS DP, pour une analyse de vos réseaus PROFIBUS DP : 24H/24

BC-502-PB

PROFIBUS DP Moniteur (BC-502-PB)

Disponibilité maximale grâce au moniteur BC-502-PB, de bus PROFIBUS DP

Le moniteur PROFIBUS DP ( BC-502-PB) est un « inspecteur » de reseaux. Il analyse de façon continue, les données qui transite sur le réseau PROFIBUS DP..Dans le cas ou l’outils detecte un echange critique qui pourrait amener à une panne du réseau, il génère automatiquement une notification de disfonctionnement et une action préventive peut être effectué.

  • Prévient de pertes de production dans le cas de problèmes de bus
  • Permets la planification des maintenance réseaux
  • Facile a utiliser, via une interface Web intégré
  • Etat de chaque esclave sur le bus PROFIBUS DP

le BC-502-PB permet la détections rapide des problèmes de bus

Le moniteur PROFIBUS se fixe dans un rack de contrôle, ( Rail DIN ). On dispose d’un moniteur par ligne de bus PROFIBUS, indépendement du nombre physique de segments a analyser. Le BC-502-PB détecte les déteriorations de la communication du bus et les rapporte. Cela permet d’établir une stratégie  de maintenance, qui réduit les interventions des équipes, seulement en cas de besoin. Les ressources maintenance sont alors optimisées.

Le BC-502-PB permet une lecture facile et simple.

Aucun changement d’adresse ni même de programmation de la PLC n’est nécessaire., lors de l’installation du moniteur PROFIBUS. La configuration et la visualisation sont fait via le réseau, grâce à une interface web intégrée.  le debug, l’analyse des problèmes demande une connaissance minimum des réseaux PROFIBUS.

 

Le BC-502-PB  avertit des pannes prochaines….

En se connectant sur un segment PROFIBUS, le moniteur PROFIBUS détecte automatiquement, la vitesse de transmission ( Baud Rate ) et démarre instantanément l’analyse du réseau PROFIBUS DP. Il détermine les temps de cycles et compte les événements critiques. Les événements critics sont : les erreurs de trames, redémarrage, les messages de diagnostics.. De cette manière, les détériorations lentes du réseau, dû à l’age de l’installation, sont rapidement détectées. Quand le nombre d’erreurs dépasse une limite par unité de temps, le moniteur PROFIBUS envoie une alarme à la PLC via un contact, ou ( optionel) vers le réseau Ethernet. Les 100 dernières alarmes sont stockées sous forme de liste. Dans le cas d’une apparition d’alarmes, le BC-502-PB permet de retrouver l’historique de la période en question. Le fichier trace peut etre analysé ultérieurement grâce à l’outil PROFIBUS Diagnostics Suite.

 

Power Supply DC 24 V +/–20%, typ. 0.3 A, max. 1 A
PROFIBUS PROFIBUS Protocols: DP, DPV1, FMS, MPI; Connection: 9-Pin D-Sub, Baud Rates: 9.6 Kbit/s .. 12 Mbit/s
Ethernet 100BASE-TX, 10BASE-T, Connection: RJ45, IP Address: Manually or via DCHP
RS232 Reserved
USB Only available with BC-502-PB/CL Option
Control Signals Potential-free Contact, 3 Inputs DC 24 V, Active High
Dimensions HxWxD: 131 x 47 x 111 mm
Weight Approx. 0.4 kg
Mounting 35 mm DIN Rail
Protection Class IP20
Operating Temperature 5 °C to 55 °C
Storage Temperature –20 °C to 70 °C
Conformity CE, FCC, VCCI
Display & Parameterization Via Integrated Web Interface
Snapshot Analysis Via PROFIBUS Diagnostics Suite PC Software, see separate Data Sheet
BC-502-PB PROFIBUS Monitorr for Continuous Bus Monitoring and Condition-based Maintenance of DP/DPV1/FMS/MPI, DIN Rail Mounted, External 24 VDC Power Supply Required, Signaling
Contact, Control Inputs, Ethernet 10/100BASE-T(X),RJ45, Integrated Web Server, User Manual, PB-DIAG-SUITE Analysis Software (See seperate Tab.)
BC-502-PB-START PROFIBUS Monitor Start Package Consisting of BC-502-PB, BC-131-PB, AC Adapter/Cable, Patch/Crossover Cable and Carrying Case

Additional Products and Services

BC-131-PB Optional Active Connection Cable for Hassle-free Integration into Existing or Running Installations Without Recabling or the Disturbances Caused by a Spur Cable, 3m Length, Bus-powered Internal Repeater
BC-502-PB/CL “Comfort Line” Option, Allows Full-Featured Protocol Analysis via USB, Supplied as Activation Code
BC-502-PB/SNMP “Premium Line” Option, Provides SNMP Network Interface for Measurement Data, Supplied as Activation Code
BC-502-PB/CLP “Comfort Line Plus” Option, Allows Full-featured Protocol Analysis via USB and Provides SNMP Network Interface for
Measurement Data, Supplied as Activation Code
TRA-PB-TECH PROFIBUS Technology Training, 2-Day
TRA-PB-TS PROFIBUS Troubleshooting Training, 3-Day

Universal Software for All Diagnostic Tools of the bus check Family

PC software for performing, evaluating and managing tests of bus physics, bus communication and cabling in PROFIBUS networks. The application is extremely easy to use, with a quick test available at a click of the mouse.BC-502-PB

One Software for All Diagnostic Products

  • Comprehensive analysis of PROFIBUS DP and PROFIBUS PA networks
  • Diagnostic functionality available depending on connected test tool
  • License-free use on any number of PCs – no activation required

Suitable for the Fieldbus Novice

  • Bus test initiated with a single mouse click
  • Clear, easy-to-read display of test results
  • Separate expert mode providing in-depth diagnostic features for network specialists

Functionality for All Diagnostic Tasks

  • Continuous display of current bus status in status bar
  • Overall bus health indicated by traffic light symbols for bus physics and bus communication
  • Detail views with additional diagnostic information, also for advanced analyses by experts
  • Testing of bus and connected devices via integrated master simulator without configuration or parameterization
  • Generation of test reports for acceptance testing of PROFIBUS installations

Functionality of the Test Tools

BC-502-PB

Technical Data

Operating Systems:
PC Hardware*
RAM 500 MB for Windows XP
1 GB for Windows 7, Windows 8
Processor 1 GHz for recording at baud rates up to 1.5 Mbit/s
2 GHz for recording at baud rates over 1.5 Mbit/s
Screen Resolution 1024 x 768 pixels (XGA)
USB Interface 2.0
Supported Operating Systems Windows XP, Windows 7, Windows 8

* The above minimum requirements are only general guidelines. Requirements may vary depending on the PC/notebook used.

Order Number

PB-DIAG-SUITE PROFIBUS Diagnostics Suite

Scope of Delivery

Software PROFIBUS Diagnostics Suite, PC software on CD-ROM for PROFIBUS Tester 5 BC-700-PB, PROFIBUS Tester 4 BC-600-PB and PROFIBUS Monitor BC-502-PB
Documentation Manual “Getting Started”

Additional Products and Services

TRA-PB-TECH PROFIBUS Technology Training, 2 Days
TRA-PB-TS PROFIBUS Troubleshooting Training, 3 Days

Fieldbus Shield Digital Leakage Current Clamp – Locating EMC Problems

Measures leakage currents, e.g. leakage and fault currents, and current pick-up of instruments without breaking the circuit. Measurements according to DIN VDE 0701/0702 and the German BetrSichV (BGV A3, VBG 4).
  • Reliably Detects Even Very Small Improper Shield Currents Resulting from EMC Problems.
Fieldbus Shield Digital Leakage Current Clamp

Functionality

Included in Package

  • Leakage current measurement
  • Differential current measurement
  • Voltage and resistance measurement
  • Frequency range for AC current / voltage 40 Hz…1 kHz
  • Acoustical continuity test
  • MIN/MAX and relative value measurement
  • Manual selection of the measurement range
  • Integrated data hold
  • Additional analog bar graph display
  • Clamp opening 30 mm
  • Auto power off
Digital leakage current clamp, 2 batteries 1.5 V IEC LR6, carrying case, measuring cables (1 x red, 1 x black) and user manual.

Order Number:

PB-LSZ-CHB3


Interface for Providing an Access Point to Test PROFIBUS Networks if the D-sub Connectors have no Service Socket or if the Devices are Connected via Terminal Block

Provides an access point for testing PROFIBUS networks if the D-sub connectors have no service socket or if the stations are connected via terminal block.
  • Allows Testing the Bus During Operation
  • Exchange of Bus Devices at the Beginning or End of the Bus Without Causing Problems on the Bus
D-Sub Service Interface

Application

The service interface is top hat rail mounted. An external 24 VDC power source is required for power supply to the terminating resistor in the PROFIBUS connector included in the package. The service interface can thus be used as an active bus termination at the beginning or end of the bus. If the PLC allows dropping and adding bus stations on the live bus, the service interface offers the possibility to exchange the first and last bus stations without causing problems on the bus. Application example:Application Example D-Sub Service Interface

Included in Package

PBMB adapter and 90° angled PROFIBUS connector with switchable terminating resistor, strain relief and screw terminal technology.

Order Number:

BC-PBMB-PB-S


Interface for Providing an Access Point to Test PROFIBUS Networks With M12 Connectors

Provides an access point for testing PROFIBUS networks with M12 connectors.
  • Allows Testing the Bus During Operation
M12 Service Interface

Application

The service interface is inserted between two bus stations. When not in use, the service output of the T piece is closed with an end cap. At baud rates of 1.5 Mbit/s or higher, use the supplied cable to ensure that the required minimum distance between bus stations is maintained. Application example:

Application Example M12 Service Interface

Downloads

Included in Package

T piece (protection class IP68) with end cap and a 1 m DP cable fitted with a male/female M12 connector on each end.

Order Number:

BC-M12DP-PB


PB-PRO1-PCIE

Carte universelle PROFIBUS, format PCI Express, pour une utilisation Maitre ou Esclave

Simple ou double canaux, l’interface PB-PRO1 est une interface au format PCI Express pour l’intégration de PC/ Servers dans une architecture PROFIBUS. la carte PB-PRO1-PCIE, permet d’utiliser vos PC comme « contrôleur », Système de contrôle d’applications et panneau opérateur.

Support of PROFIBUS Master or Slave Functionality

The protocol required for the specific use case is user selectable and executed on the PBpro PCI Express board. As a DP slave, the board integrates the PC into overlying control architectures. Configured as a DP master, the board turns the PC itself into the controller. As a DP Master Class 2, it provides the basis for parameterization and asset management tasks. In addition, integration into FMS systems or proprietary applications is just as easy and unproblematic as direct access at the lowest protocol level (FDL). This makes the PBpro PCI Express a universal interface solution and allows manufacturers to optimize the overhead costs and the inventory for their PROFIBUS options.

Rapid Integration With the Right Software Interface

The included PROFIBUS driver software is complemented with many sample programs that demonstrate how to use the PROFIBUS API. Commented sample programs show how this is done. A matching Softing OPC Server, which is available as an optional standard interface, quickly and easily connects any application that has an integrated OPC client. Typical applications include visualization, SCADA or MES systems. FDT compliant parameterization tools use the PROFIdtm Communication DTM from Softing as a link to the board. Used with the free STEP7 driver, the board can also provide a PG/PC adapter for programming Siemens controllers.

Application in a Wide Variety of Target Systems

In addition to standard Windows environments, the PBpro PCI Express board also supports Windows CE.NET as a real-time environment. On request, Softing’s team of engineers can customize the board according to customer specifications.

Master/Slave, Single Channel 1)  Slave, Single Channel 1) Master/Slave, Dual Channel
PROFIBUS Protocol
DP-V0 Master PB-PRO1-PCIE PB-PRO1-PCIE
DP-V1 Master: Acyclic C2 Services PB-PRO1-PCIE PB-PRO1-PCIE
FMS PB-PRO1-PCIE PB-PRO1-PCIE
FDL PB-PRO1-PCIE PB-PRO1-PCIE
DP-V0 Slave PB-PRO1-PCIE PB-PRO1-PCIE PB-PRO1-PCIE
Fieldbus Connection 9-Pin D-Sub Female, RS485, Galvanically Isolated
Transfer Rates 9.6; 19.2; 45.45; 93.75; 187.5; 500; 1500; 3000; 6000; 12000 Kbit/s
PC Interface PCI Express x1 According to PCIe r1.0a and CEM 1.1, 512 KB Shared RAM per Channel
Operating Temperature 0 oC .. +55 oC
Storage Temperature -20 oC .. +70 oC
Relative Humidity < 90%, Non-Condensing
Dimensions [mm] 168 x 69  168 x 69 168 x 103
Power Supply
Supply Voltage 3.3V / 12V (± 5%) DC
Current Consumption [mA] typ. 500 / 90 typ. 500 / 90 typ. 640 / 170
Drivers available for Windows 2000, Windows XP, Windows Vista, Windows 7, Windows 8, Windows 10
Conformity PB-PRO1-PCIE

Downloads

  • Drivers & Software

    • PROFIBUS GSD files
  • Articles & White Papers

  • Certificates

  • Data Sheets

PB-PRO 1-PCIE (PB-PRO 1-PCIE/LP1)) Master/Slave, Single Channel 1)
PB-PRO 1S-PCI E(PB-PRO 1S-PCIE/LP1)) Slave, Cingle Channel 1)
PB-PRO 2-PCIE Master/Slave, Dual Channel

Scope of Delivery

PC interface Board, CD with Drivers, Documentation and Sample Programs

Additional Products and Services

OPC-PB PROFIBUS OPC Server for DP-V0 / DP-V1
DCF-DY-4100 OPC Server for S7 / S5
TRA-PB-TECH PROFIBUS Technology Training

1) Also Available with Low Profile Slot Bracket

THLink – PROFINET

PROFINET : THLink Profinet

Diagnostic PROFINET : Indépendant du contrôleur

L’outil de diagnostic THLink PROFINET est totalement indépendant du contrôleur. Il permet le « monitoring » des réseaux PROFINET.  Les données sont collectés dans des réseaux comprenant jusqu’à 254 Noeuds et mise à la disposition des utilisateurs via le logiciel THScope. THLink PROFINET facile d’utilisations’intègre facilement sans intéraction avec le fonctionnement de l’installation existante.

Independent Access to PROFINET Network

  • Controller-independent
  • Independent of configuration tools
  • Only one tool needed to monitor multiple IP subnetworks (up to 254 nodes, one or more controllers)

Designed for Installation without Interference with Plant Operation

  • Connection to free port in PROFINET network, also possible during operation of the plant
  • No need to install TAPs or use mirror ports
  • Highest security (separate accesses for control room level and plant level, no routing)
  • Easy integration into existing plants thanks to compact design

Powerful Data Collection Capabilities Optimized for PROFINET

  • Collection from PROFINET devices and other nodes (e.g. PCs or camera systems)
  • PROFINET supervisor in PROFINET networks
  • Network load limit according to PROFINET guidelines

Optimized for Use by Maintenance Engineers

  • Suitable for network acceptance testing, continuous monitoring and troubleshooting
  • Easy and intuitive handling and operation
  • Fault identification with intelligent troubleshooting assistance
  • Seamless integration with TH SCOPE diagnostics software
Functionality
  • Network detection and data collection (active/passive for PROFINET Networks)
  • Alarm notification in case of fault
  • Basic monitoring, configuration
  • Integrated web server
Input Voltage 24 VDC (18 VDC … 32 VDC)
Current consumption max. 180 mA
Current consumption relay contact max. 100 mA
Operating Temperature -40 °C … +75 °C
Relative Air Humidity 5 … 95 % (no condensation)
Ethernet Ports RJ-45 (10Base-T/100Base-TX)
Supported SD Cards See Release Notes
Mounting 35 mm DIN rail
Dimensions (HxWxD) 22.5 x 99 x 114.5 mm
Weight 120 g
Certifications CE
GDA-JA-003034 TH LINK PROFINET

Scope of Delivery

Hardware TH LINK PROFINET
Documentation Installation Manual, Release Note (by download)

Additional Products and Services

LRA-JY-003024 TH SCOPE (software key)
LRL-JY-003025 TH SCOPE (hardware key)
LRA-JY-003028 TH LINK PC Industrial Ethernet (software key)
LRL-JY-003029 TH LINK PC Industrial Ethernet (hardware key)
GDA-JY-003037 TH LINK Industrial Ethernet
TRA-PN-TECH Training “PROFINET Technology”
TRA-PN-CERTENG Training “PROFINET Commissioning and Troubleshooting”

TH LINK:
enablement of the following ports:

  • HTTP Protocol:      80 TCP
  • Firmware update: 1100 TCP
  • communication with each other:    1123, 1124, 2364 UDP
  • communication with TH SCOPE via Multicast:  2364 UDP
  • communication with TH SCOPE via Unicast:    1151, 2365 UDP

There must be no firewall between the TH LINK and the PROFINET and/or EtherNet/IP devices.

TH SCOPE:
If your network is protected by a second firewall in addition to the Windows firewall, make sure that the following settings are made to allow TH SCOPE services to communicate properly.

  • Enabling of HTTP port 80 – inbound and outbound
  • Enabling of SNMP port 161 inbound or port 2367 (if port 161 is used by another SNMP agent).
  • Enabling of IP 224.0.5.128 port 2364 UDP outbound
  • Enabling of UDP ports 2365 outbound and 2366 inbound

 

The following ports are used by TH SCOPE for internal communication only:

  • Port 22
  • Port 80
  • Port 1100
  • Ports 1123 – 1151
  • Port 1500
  • Port 1501
  • Ports 2363 – 2366
  • Ports 49152 – 49171