PROFINET : THLink Profinet

Diagnostic PROFINET : Indépendant du contrôleur
L’outil de diagnostic THLink PROFINET est totalement indépendant du contrôleur. Il permet le « monitoring » des réseaux PROFINET. Les données sont collectés dans des réseaux comprenant jusqu’à 254 Noeuds et mise à la disposition des utilisateurs via le logiciel THScope. THLink PROFINET facile d’utilisations’intègre facilement sans intéraction avec le fonctionnement de l’installation existante.
| Functionality | 
  | 
| Input Voltage | 24 VDC (18 VDC … 32 VDC) | 
| Current consumption | max. 180 mA | 
| Current consumption relay contact | max. 100 mA | 
| Operating Temperature | -40 °C … +75 °C | 
| Relative Air Humidity | 5 … 95 % (no condensation) | 
| Ethernet Ports | RJ-45 (10Base-T/100Base-TX) | 
| Supported SD Cards | See Release Notes | 
| Mounting | 35 mm DIN rail | 
| Dimensions (HxWxD) | 22.5 x 99 x 114.5 mm | 
| Weight | 120 g | 
| Certifications | CE | 
- 
Data Sheets
 - 
Drivers & Software
 - 
Manuals & Documentation
 
| GDA-JA-003034 | TH LINK PROFINET | 
Scope of Delivery
| Hardware | TH LINK PROFINET | 
| Documentation | Installation Manual, Release Note (by download) | 
Additional Products and Services
| LRA-JY-003024 | TH SCOPE (software key) | 
| LRL-JY-003025 | TH SCOPE (hardware key) | 
| LRA-JY-003028 | TH LINK PC Industrial Ethernet (software key) | 
| LRL-JY-003029 | TH LINK PC Industrial Ethernet (hardware key) | 
| GDA-JY-003037 | TH LINK Industrial Ethernet | 
| TRA-PN-TECH | Training “PROFINET Technology” | 
| TRA-PN-CERTENG | Training “PROFINET Commissioning and Troubleshooting” | 
TH LINK:
enablement of the following ports:
- HTTP Protocol: 80 TCP
 - Firmware update: 1100 TCP
 - communication with each other: 1123, 1124, 2364 UDP
 - communication with TH SCOPE via Multicast: 2364 UDP
 - communication with TH SCOPE via Unicast: 1151, 2365 UDP
 
There must be no firewall between the TH LINK and the PROFINET and/or EtherNet/IP devices.
TH SCOPE:
If your network is protected by a second firewall in addition to the Windows firewall, make sure that the following settings are made to allow TH SCOPE services to communicate properly.
- Enabling of HTTP port 80 – inbound and outbound
 - Enabling of SNMP port 161 inbound or port 2367 (if port 161 is used by another SNMP agent).
 - Enabling of IP 224.0.5.128 port 2364 UDP outbound
 - Enabling of UDP ports 2365 outbound and 2366 inbound
 
The following ports are used by TH SCOPE for internal communication only:
- Port 22
 - Port 80
 - Port 1100
 - Ports 1123 – 1151
 - Port 1500
 - Port 1501
 - Ports 2363 – 2366